Bus Coupler, Local-Master
Remote Coupling Unit for
.. TCP/IP (via LAN/WLAN)
.. CAN (via CAN2.0)
.. Serial (via RS485, RS232)
Description
The LWCS is a connection device between a remote-master and a string of the brickBUS® slaves modules.
The largest configuration (variant) contains the interfaces LAN, WLAN, CAN and Serial which can be used to couple a remote-master. It is also possible to use the CAN and RSxxx as an IO-device (on request).
The unit is driven by 24Vdc and also serves as power-supply unit that delivers 3.3V and 24V for the slave modules. Nevertheless the bus is controlled by the connected remote-master. The LWCS acts as the bus master of the local bus and the connected slaves modules. There-fore the LWCS has the ability to control its string in exceptional situations autark, e.g. by put-ting a teached output pattern on the bus when the remote-master communication breaks down.
Operation Modes
The LWCS acts as a coupling device between remote-bus and local-bus and is therefore a Lo-cal-Master whitout own functionality. It contains three different (alternative) operation modes:
- Serial Operation (via RS485)
- CAN Operation (via CAN-Interface)
- TCP/IP Operation (via LAN of WLAN)
All three modes contain the same data and protocol content.
For the TCP/IP communication and div. common programming systems, ready drivers are available (MSVC++, Gamma). See => eB_Developer-Manual, .
For own/individual programming of connections to the LWCS see eB_Developer-Manual.
Z-CouplingBrick-01
ID
1-601
module size
72mm x 99mm
OS / Kernel
1x FreeRTOS
(Mass) Data Storage
1x EEPROM
1x Data-Flash
Interfaces (besides brickBUS)
1x RS232
1x RS485
1x CAN
1x LAN-Ethernet
1x WLAN
Power Supply(needed) and Globals
12…24V
Notes
with all features
Z-CouplingBrick-02
ID
1-602
module size
72mm x 99mm
OS / Kernel
1x FreeRTOS
(Mass) Data Storage
1x EEPROM
1x Data-Flash
Interfaces (besides brickBUS)
1x RS232
1x RS485
1x CAN
1x LAN-Ethernet
Power Supply(needed) and Globals
12…24V
Notes
no WLAN
Z-CouplingBrick-03
ID
1-603
module size
72mm x 99mm
OS / Kernel
1x FreeRTOS
(Mass) Data Storage
1x EEPROM
1x Data-Flash
Interfaces (besides brickBUS)
1x LAN-Ethernet
Power Supply(needed) and Globals
12…24V
Notes
only LAN
Z-CouplingBrick-04
ID
1-604
module size
72mm x 99mm
OS / Kernel
1x FreeRTOS
(Mass) Data Storage
1x EEPROM
1x Data-Flash
Interfaces (besides brickBUS)
1x RS232
1x RS485
1x CAN
Power Supply(needed) and Globals
12…24V
Notes
only RSxx. CAN